87 Paradigm Architectural Control Processor Configuration Manual
2 and 3 Wire Fluorescent Mode
Property Units Default 120V Default 230V Default 277V
Curve not applicable Linear Linear Linear
Voltage Regulation On / Off On On On
Pre-Heat On / Off Off Off Off
Dynamic Preheat seconds 0sec / Off 0sec / Off 0sec / Off
Min Scale Volts 56V 108V 130V
Max Scale Volts 120V 230V 277V
Transformer Mode On / Off On On On
Threshold Control 1% (>0%) 1% (>0%) 1% (>0%)
4 Wire Fluorescent Mode
Property Units Default 120V Default 230V Default 277V
Curve not applicable Linear Linear Linear
Voltage Regulation On / Off Off Off Off
Pre-Heat On / Off Off Off Off
Dynamic Preheat seconds 0sec / Off 0sec / Off 0sec / Off
Min Scale Volts 120 =Max 230 =Max 277 =Max
Max Scale Volts 120 230 277
Transformer Mode On / Off On On On
Threshold Control 1% (>0%) 1% (>0%) 1% (>0%)
Always On Mode
Property Units Default 120V Default 230V Default 277V
Curve not applicable Linear Linear Linear
Voltage Regulation On / Off Off Off Off
Pre-Heat On / Off Off Off Off
Dynamic Preheat seconds 0sec / Off 0sec / Off 0sec / Off
Min Scale Volts 120 =Max 230 =Max 277 =Max
Max Scale Volts 120 230 277
Transformer Mode On / Off Off Off Off
Threshold Control 0 0 0
DALI Mode
Property Units Default 120V Default 230V Default 277V
Curve not applicable Linear Linear Linear
Voltage Regulation On / Off Off Off Off
Pre-Heat On / Off Off Off Off
Dynamic Preheat seconds 0sec / Off 0sec / Off 0sec / Off
Min Scale Volts 120 =Max 230 =Max 277 =Max
Max Scale Volts 120 230 277
Transformer Mode On / Off On On On
Threshold Control 0 0 0